[内部错误 23] InFN .......................................................................................................... 621
[内部错误 25] InFP .......................................................................................................... 622
[内部错误 27] InFr .......................................................................................................... 622
[内部错误 28] InFS .......................................................................................................... 623
[内部错误 29] InFt .......................................................................................................... 623
[内部错误 30] InFU .......................................................................................................... 624
[内部错误 31] InFV .......................................................................................................... 624
[入口压力错误] iPPF ........................................................................................................ 625
[自整定错误] tnF ................................................................................................................. 658
[过程欠载] ULF...................................................................................................................... 659
[AFE 主电源欠压] UrF ...................................................................................................... 659
[主电源欠压] USF................................................................................................................. 660
[VxCtrl 错误] vcf............................................................................................................. 660
如需对变频系统进行检修,请遵循下表指示的步骤:
步骤 | 操作 |
1 | 断开所有电源,包括可能会带电的外部控制电源。 |
2 | 将所有电源隔离开关锁定在断电位置。 |
3 | 等待 15 分钟,让直流母线电容充分放电(变频器的LED 并不是有无直流母线电压的指示灯)。 |
4 | 测量PA/+ 和PC/- 端子之间的直流母线电压,确保该电压低于 42 Vdc。 |
5 | 如果直流母线电容未完全放电,请与当地的施耐德电气办事处联系。不要对变频器进行修理或运行。 |
6 | 查找并纠正检测到的错误的原因。 |
7 | 恢复对变频器供电,以确认已纠正检测到的错误。 |
故障原因消除后, 可以通过以下操作任一清除错误警告:
• 关闭变频器。
• 使用 [产品重启] RP 参数。
• 使用分配给 [产品重启分配] RPA 的数字输入或控制位。
• 使用 [故障自动复位] ATR- 功能。
• 数字输入或控制位设置为 [故障复位] RST- 功能。
◦ 对于 [故障复位分配] RSF 和 [扩展故障复位] HRFC,请参阅 [故障复位]
RST- 菜单。
• 按图形显示终端上的停止/复位键,具体取决于 [停止键启用] PST 的设置。
下表总结了在消除原因后清除检测到的错误的可能性:
如何在消除原因后清除错误代码 | 已清除错误的列表 |
• 关闭变频器。 • 使用 [产品重启] RP 参数。 • 使用分配给 [产品重启分配] RPA 的数字输入或控制位。 | 检测到的所有错误。 |
• 消除原因后即清除。 | CFF, CFI, CFI2, CFI3, CSF, FWER, HCF, PGLF, PHF, URF, USF |
• 使用分配给以下对象的数字输入或控制位 [故障复位分配] RSF. • 按 HMI 面板上的复位按钮。 | ACF1, ACF2, ACF3, ASF, MFF, SOF, TNF |
如何在消除原因后清除错误代码 | 已清除错误的列表 |
• 使用分配给以下对象的数字输入或控制位 [故障复位分配] RSF. • 按 HMI 面板上的复位按钮。 • 使用 [故障自动复位] ATR- 功能。 | CFA, CFB, CFC, CHF, CNF, COF, COPF, DRYF, EPF1, EPF2, ETHF, FCF2, FDR1, FDR2, FFDF, HFPF, IDLF, IFA, IFB, IFC, IFD, IHF, INF9, INFB, INFV, IPPF, JAMF, LCF, LCHF, LCLF, LFF1, LFF2, LFF3, LFF4, LFF5, LKON, MDLF, MOF, MPDF, MPLF, OBF, OBF2, OHF, OLC, OLF, OPF1, OPF2, OPHF, OPLF, OSF, P24C, PCPF, PFMF, PLFF, SCF4, SCF5, SLF1, SLF2, SLF3, STF, T2CF, T3CF, T4CF, T5CF, TFA, TFB, TFC, TFD, TH2F, TH3F, TH4F, TH5F, TJF, TJF2, ULF |
如果 [扩展故障复位] HRFC 设置为 YES: • 使用分配给 [故障复位分配] RSF 的数字输入或控制位; • 按图形显示终端上的停止/复位键,具体取决于 [停止键启用] PST 的设置。 | CRF1, INFD, SCF1 |
SHAPE \* MERGEFORMAT
[AFE 直流电容器故障] ACF1
AFE 直流电容器故障: 直流电容器过电流。
• 电源电压过低的持续时间过长。
• 电源电压达到下限,AFE 的调制率提高,有助于保护直流链路电容器,防止触发 [AFE 直流电容器故障] ACF1。
• 检查电源电压。
• 检查电源电压的参数设置。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
[AFE 电流控制故障] ACF2
电源电压中断。
• 检查电源电压。
• 降低电压下降次数。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AFE 线路滤波器故障] ACF3
发电机运行期间出现电源电压下降。
检查电源电压。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
[高级功能锁] AFLF
[液位控制策略] LCst 设置为 [能效优化] ADV 并给出运行命令。
请与您当地的Schneider Electric 代表联系。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[角度错误] ASF
在相位移夹角测量过程中,如果电机相断开或电机电感太高,则会触发此错误。
• 检查电机连接是否缺相,以及变频器允许的最大电流。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
[断路器故障] CbF
在配置的 [电源电压超时] LCt过后,与断路器逻辑控制(启动或停止脉冲)相比,直流总线电压水平不正确。
• 检查断路器逻辑控制(启动和停止的脉冲时间)。
• 检查断路器的机械状态。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
监控功能检测到了一个错误。 当检测到的故障的持续时间超过 [机柜电路A 延迟]
CFAA 时,分配至 [机柜电路 A 分配] FdA 的数字输入将被激活。
• 确定检测的原因。
• 检查连接的设备(门开关、热开关等)及其接线。
• 检查 [机柜电路 A 分配] CFAA 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
监控功能检测到了一个错误。当检测到的故障的持续时间超过 [机柜电路B 延迟]
FdB 时,分配至 [机柜电路 B 分配] CFAB 的数字输入将被激活。
• 确定检测的原因。
• 检查连接的设备(门开关、热开关等)及其接线。
• 检查 [机柜电路 B 分配] CFAB 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
监控功能检测到了一个错误。 当检测到的故障的持续时间超过 [机柜电路C 延迟]
CFAC 时,分配至 [机柜电路 C 分配] FdC 的数字输入将被激活。
• 确定检测的原因。
• 检查连接的设备(门开关、热开关等)及其接线。
• 检查 [机柜电路 C 分配] CFAC 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[配置不正确] CFF
• 选件模块已更换或拆除.
• 使用变频器上配置的具有不同额定值的控制卡替换现有控制卡。
• 当前配置不一致。
• 检查选件模块上未出现检测出错误。
• 如果专门更换了控制块,请参阅以下注释。
• 如果允许,返回到出厂设置或恢复备份配置。
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[无效配置] CFI
无效配置。
通过调试工具或现场总线加载至变频器的配置与变频器软硬件不一致。
• 检查已加载的配置。
• 加载有效配置。
This detected error is cleared as soon as its cause has been removed.
[配置传输错误] CFI2
• 将配置传输到变频器的操作失败或中断。
• 加载的配置与该变频器不兼容。
• 检查以前加载的配置。
• 载入兼容配置。
• 使用PC 软件调试工具传输兼容的配置
• 执行出厂设置
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[预设置传输故障] CFI3
将配置传输到变频器的操作失败或中断。
请与您当地的Schneider Electric 代表联系。
This detected error is cleared as soon as its cause has been removed.
[机柜过热故障] CHF
机柜热开关处于激活状态,机柜风扇已开启,但无风扇反馈。
配有机柜 IO 的变频器的数字输入 DI50 和 DI51 配置为用于监测机柜温度。在温度过高的情况下,如果机箱温度开关打开,将触发 [机柜过热故障] CHF。
此错误只能在运行状态下触发。在其他状态下,将激活 [机柜过热警告] CHA。
• 检查机柜风扇及其接线。
• 检查机箱中的温度是否太高。
• 检查热开关的设置(必须为 60°C (140°F))
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[现场总线通信中断] CnF
现场总线模块的通信中断。
当现场总线模块与主站(PLC) 之间的通信中断时,将触发此错误。
• 检查环境(电磁兼容性)。
• 检查接线情况。
• 检查超时。
• 更换选件模块。
• 请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
CANopen® 现场总线上的通信中断。
• 检查通信总线。
• 检查超时。
• 请参考CANopen® 手册 (EAV64333), 15 页。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[冷却泵故障] COPF
冷却泵未在工作。
请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[预充电电容器] CrF1
• 充电电路控制检测到了错误或充电电阻器损坏。
• 电源电压太低。
• 对变频器断电再通电。
• 检查内部连接。
• 检查 [欠压处理] usb 的电压和参数。
• 请与您当地的Schneider Electric 代表联系。
This detected error can be cleared manually with the [扩展故障复位] HRFC
parameter after the cause has been removed.
SHAPE \* MERGEFORMAT
[AFE 接触器反馈错误] CrF3
此错误在不同情况下发生(启动/停止/操作过程中)。
在每个AFE 功能块内部相互独立地分析此错误。 如果 AFE 电源接触器反馈信号与内部AFE 电源接触器命令不匹配,将会触发 [AFE 接触器反馈错误] CrF3。
执行运行命令时:
• AFE 模块内部控制发送“主接触器开启命令”后,必须在 400 毫秒内收到“主接触器开启反馈”。
执行停止命令时:
• 在 AFE 模块内部控制已发送“主接触器关闭命令”后,必须在 500 毫秒内收到
“主接触器关闭反馈”。
• 检查与以下各项相关的环境(电磁兼容性):
◦ 电缆敷设(控制单元和功率单元未混合)。
◦ 接地线缆。
◦ 接地屏蔽层。
• 检查将变频器连接到电机的电缆。
• 确定哪个 AFE 模块检测到 [AFE 接触器反馈错误] CrF3 错误,方法是将图形显示终端连接到 AFE 模块 HMI 端口并检查故障历史记录。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[通道切换错误] CSF
切换到无效通道。
检查功能参数。
This detected error is cleared as soon as its cause has been removed.
[直流母线纹波错误] DCRE
在直流母线或直流母线电容器损坏时观测到持续的纹波。
• 对变频器断电再通电。
• 检查输入滤波器的行为是否正确。
• 检查电源接线。
• 检查内部连接。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[干泵运行错误] drYF
干泵运行监控功能检测到了一个错误。
注: 触发错误后,即使已清除检测到的错误,在 [干泵运行重启延时] dryr
结束前,也无法重启泵。
• 检查泵已充分泡水。
• 检查入水管道有无漏气。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[EEPROM 控制] EEF1
检测到了控制块的内存错误。
• 检查环境(电磁兼容性)。
• 关闭产品电源。
• 还原出厂设置。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[EEPROM 功率] EEF2
检测到了电源板的内存错误。
• 检查环境(电磁兼容性)。
• 关闭产品电源。
• 还原出厂设置。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[外部错误] EPF1
• 由外部设备触发的事件,由应用引起。
• 由嵌入式以太网触发的外部错误。
• 该错误由外部电路导致。
• 以太网配置文件损坏。
• 消除外部错误的原因。
• 执行以太网配置的出厂设置或修改 IP 模式。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[现场总线错误] EPF2
由外部设备触发的事件,由应用引起。
消除外部错误的原因。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[嵌入式以太网通信中断] EtHF
ModbusTCP 总线出现通信中断。
• 检查通信总线。
• 请参阅以太网手册 (嵌入式(EAV64327), 15 页;选件(EAV64328), 15 页)。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[输出接触器闭合故障] FCF1
虽然符合打开条件,但输出接触器仍闭合。
• 检查输出接触器及其接线。
• 检查接触器反馈接线。
This detected error requires a power reset.
[输出接触器打开错误] FCF2
虽然符合闭合条件,但输出接触器仍打开。
• 检查输出接触器及其接线。
• 检查接触器反馈接线。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[FDR 1 错误] FDR1
• 嵌入式以太网FDR 错误
• 变频器和 PLC 之间的通信中断
• 配置文件不兼容、为空或无效
• 变频器额定值与配置文件不一致
• 检查变频器和PLC 连接
• 检查通信工作负载
• 重新启动将配置文件从变频器到PLC 的传输
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[FDR 2 错误] FDR2
• 以太网现场总线模块 FDR 故障
• 变频器和 PLC 之间的通信中断
• 配置文件不兼容、为空或损坏
• 变频器额定值与配置文件不一致
• 检查变频器和PLC 连接
• 检查通信工作负载
• 重新启动将配置文件从变频器到PLC 的传输
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[风扇反馈错误] FFDF
风机速度过低。
[风扇反馈警告] FFDA 已激活 10 分钟以上。
更换风机。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[固件更新错误] FWEr
固件更新功能检测到错误。
• 请与您当地的Schneider Electric 代表联系。
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[板兼容性] HCF
硬件配置错误。
[配对密码] PPI 参数已启用,且选件模块被更换。
• 重新安装原始选件模块。
• 如果已慎重更换该模块,则可通过输入 [配对密码] PPI 确认配置。
This detected error is cleared as soon as its cause has been removed.
[高流量错误] HFPF
流量高监控功能检测到了错误。
• 检查系统是否在其流量范围内运行。
• 检查系统出口处的管道有无爆裂。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[节能退出错误] IDLF
变频器未打开,即使 [节能超时] IDLT 已过。
• 检查电源/接触器/变频器接线情况。
• 检查超时。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [监视回路A 分配] IFAA 的数字输入的有效时间超过 [监视回路A 延时]
IFdA。
• 检查连接的设备及其接线。
• 检查 [监视回路 A 分配] IFAA 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
分配至 [监视回路B 分配] IFAb 的数字输入的有效时间超过 [监视回路B 延时]
IFdB。
• 检查连接的设备及其接线。
• 检查 [监视回路 B 分配] IFAB 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [监视回路C 分配] IFAC 的数字输入的有效时间超过 [监视回路C 延时]
IFdC。
• 检查连接的设备及其接线。
• 检查 [监视回路 C 分配] IFAC 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
分配至 [监视回路D 分配] IFAD 的数字输入的有效时间超过 [监视回路D 延时]
IFdD。
• 检查连接的设备及其接线。
• 检查 [监视回路 D 分配] IFAD 参数的分配。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[输入过热] iHF
AFE 功率模块温度过高。
检查变频器通风情况和环境温度。 等待变频器冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[内部连接错误] ILF
选件模块和变频器之间的通信中断。
• 检查环境(电磁兼容性)。
• 检查连接状况。
• 更换选件模块。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 0] InF0
• 控制板的微处理器之间的通信中断。
• 电源板额定功率无效。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 1] InF1
电源板额定功率无效。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 2] InF2
电源板与控制板软件不兼容。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
检测出内部通信错误。
• 检查变频器控制端子(模拟输入的内部 10V 电源已超载)的接线。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 4] InF4
内部数据不一致。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 6] InF
• 安装在变频器中的选件无法识别。
• 不存在或无法识别可插拔的控制端子模块(如果有)。
• 无法识别嵌入式以太网适配器。
• 与变频的固件版本的兼容性。
• 关闭变频器后,插入可插拔控制端子板。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 7] InF7
与控制板的 CPLD 组件的通信中断。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 8] InF8
内部开关电源工作不正常。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 9] InF9
检测到了电流测量电路出错。
请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[内部错误 10] InFA
电源整流部分未正常工作。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 11] InFb
变频器内部的热传感器无法正常工作。
Contact your local Schneider Electric representative.
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[内部错误 12] InFC
内部供电错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 13] InFD
差分电流偏差。
检查DigiLink 电缆 (GG45) 的连接。
请与您当地的Schneider Electric 代表联系。
This detected error can be cleared manually with the [扩展故障复位] HRFC
parameter after the cause has been removed.
SHAPE \* MERGEFORMAT
[内部错误 14] InFE
检测到内部微处理器出错。
• 检查能否清除错误代码。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 15] InFF
串行存储器闪存格式错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 16] InFG
输出继电器选件模块的通信中断或内部出错。
• 检查选件模块是否正确连接到插槽
• 更换选件模块。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 17] InFH
与数字与模拟I/O 扩展模块通信中断或数字与模拟I/O 扩展模块出现内部错误。
• 检查选件模块是否正确连接到插槽
• 更换选件模块。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 20] InF
选件模块接口板错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误21] InFl
内部实时时钟错误。这可能是面板与变频器之间出现通信错误或时钟振荡器启动出错。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 22] InF
检测到了嵌入式以太网适配器错误。
检查与以太网端口的连接。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 23] InFN
检测到控制块和AFE 或BU 模块之间的通讯中断。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 25] InFP
控制板硬件版本与固件版本之间不兼容。
• 更新固件包。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 27] InFr
CPLD 中的诊断功能已检测到错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 28] InFS
检测到AFE 模块上出现错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[内部错误 29] InFt
检测到功率模块/ 逆变器模块上出现错误。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[内部错误 30] InFU
检测到整流器模块上出现错误,或在为直流总线充电时触发了 [输入缺相] PHF。
对变频器断电再通电。
如果 [输入缺相] PHF 错误代码替换了 [内部错误 30] inFu,请参阅 [输入缺相] PHF 错误的说明,其他情况下,请联系您当地的 Schneider Electric 代表。
This detected error requires a power reset.
[内部错误 31] InFV
检测到程序块架构出错(程序块丢失)。
与当地的 Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[入口压力错误] iPPF
入口压力监控功能检测到了错误。
• 查找系统入口出现低压的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[防堵塞错误] JA F
防堵塞监控功能超出了时间窗口所规定的最大正反转动作时序数。
• 查找叶轮的堵塞物质。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[输入接触器] LCF
尽管 [输入电压超时监测] LCt 已过,变频器仍未启动。
• 检查输入接触器及其接线。
• 检查 [输入电压超时] LCt。
• 检查电源/接触器/变频器接线。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[高电平错误] LCHF
注水过程中已激活最高液位开关。
• 检查参数 [最高液位切换分配] LCWH。
• 检查相应变频器输入及其接线的状态。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[低液位错误] LCLF
排空过程中已激活最低液位开关。
• 检查参数 [最低液位切换分配] LCWL。
• 检查相应变频器输入及其接线的状态。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
模拟输入 AI1 丢失 4-20 mA 信号。
当测得的电流小于 2 mA 时,将触发此错误。
• 检查模拟输入的连接。
• 检查 [AI1 4-20mA 丢失] LFL1 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
模拟输入 AI2 损失 4-20 mA。
当测得的电流小于 2 mA 时,将触发此错误。
• 检查模拟输入的连接。
• 检查 [AI2 4-20mA 丢失] LFL2 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
模拟输入 AI3 上损失 4-20 mA。
当测得的电流小于 2 mA 时,将触发此错误。
• 检查模拟输入的连接。
• 检查 [AI3 4-20mA 丢失] LFL3 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
模拟输入 AI4 丢失 4-20 mA 信号。
当测得的电流小于 2mA 时,将触发此错误。
• 检查模拟输入的连接。
• 检查 [AI4 4-20mA 丢失] LFL4 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
模拟输入 AI5 丢失 4-20 mA 信号。
当测得的电流小于 2 mA 时,将触发此错误。
• 检查模拟输入的连接。
• 检查 [AI5 4-20mA 丢失] LFL5 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[上电锁定错误] L ON
外部设备未就绪。
检查外部设备是否分配至上电锁定输入。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[MDL 故障] dLF
• 运行时通信中断。
• 此功能检测到系统配置的不一致性。
• 检查通信网络。
• 检查多变频器链路功能的配置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
AFE 模块上的[电源频率] FAC 超出范围。
检查电源频率。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
[模块过热] OF
机柜温度过高。
[模块过热] OA 警告已激活 10 分钟以上。
检查机柜的冷却情况。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[多泵设备故障] PDF
多变频器链接架构上的一个设备缺失。
检查通信网络。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[主泵故障] pLF
选定主泵在运行中不可用。
检查对应的变频器数字输入的状态,了解泵可用性信息(例如,对于泵 1,查看
[泵 1 就绪分配] PI1)。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[直流总线过压] ObF
• 减速时间太短或驱动性负载太高。
• 供电电源电压过高。
• 延长减速时间。
• 在与该应用兼容的前提下配置 [减速斜坡自适应]brA 功能。
• 检查电源电压。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AFE 母线不平衡] ObF2
• AFE 直流母线不平衡。
• 供电电源电压过高。
• 总发电量太高
• 检查电源电压。
• 请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[过流] OCF
• [电机数据] OA- 菜单中的中的参数不正确。
• 惯量或负载过高。
• 机械堵塞。
• 检查电机参数。
• 检查电机/变频器/负载的大小。
• 检查机械装置的状态。
• 减小 [电流限制] CLI。
• 增加开关频率。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[变频器过热] OHF
变频器温度过高。
检查电机负载、变频器通风情况和环境温度。等待变频器冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[过程过载] OLC
过程过载。
• 检查并消除引起过载的原因。
• 检查 [过程过载] OLd- 功能的参数。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[电机过载] OLF
因电机电流持续过大而触发。
• 检查电机热监控的设置
• 检查电机负载。等待电机冷却后再重新启动。
• 检查以下参数的设置:
◦ [电机热电流] ITH
◦ [电机热保护类型] THT
◦ [电机热阈值] TTD
◦ [电机过热响应] OLL
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[一相输出丢失] OPF1
变频器输出中缺少一相。
检查变频器与电机的接线。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[输出缺相] OPF2
• 电机未连接或电机功率太低。
• 输出接触器打开。
• 电机电流瞬间不稳定。
• 检查变频器与电机的接线。
• 如果正在使用输出接触器,请将 [输出缺相分配] OPL 设置为 [未触发错误]
OAC。
• 如果变频器已连接一个低功率电机或未连接电机: 在出厂设置模式中,激活电机缺相检测 [输出缺相] OPL = [触发输出缺相] YES。 禁用电机缺相检测
[输出缺相] OPL = [功能未激活] nO。
• 检查并优化下列参数: [IR 定子压降补偿] UFr、[电机额定电压] UnS 以及 [电机额定电流] nCr 并执行 [自整定] tUn。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[出口压力高] OPHF
出口压力监控功能检测到了压力过高错误。
• 查找系统出口出现高压的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[出口压力低] OPLF
出口压力监控功能检测到了压力过低错误。
• 检查系统出口处的管道有无损坏。
• 查找系统出口出现低压的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[供电电源过电压] OSF
• 供电电源电压过高。
• 供电电源受到干扰。
检查电源电压。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[机柜I/O 24V 错误] P24C
输入DI58 用于监控输入端子上的 24V 电源。 如果出现故障,则抑制所有输入以避免意外错误消息(从软件版本V1.6V1.3 开始)。
• DI58 机柜 I/O 输入未连接到内部端子X231。
• DI58 由另一机柜 I/O 功能使用。
• 确认端子 X231 是否已连接到机柜 I/O 输入 DI58。
• 如果DI58 由另一机柜功能使用,则需要将该功能更改为X220 端子上的另一可用机柜 I/O 输入。 此外,还需要调整新的所选输入的参数设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[泵循环启动错误] PCPF
泵循环监控功能超出了时间窗口所规定的最大启动序列数目。
• 查找系统重复启动的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[PID 反馈错误] PF F
PID 反馈错误在时间窗口内超出了设定点周围的允许范围。
• 检查管道是否有机械故障。
• 检查是否存在漏水现象。
• 检查是否打开了排放阀。
• 检查是否打开了消防栓。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[程序加载错误] PGLF
检查能否清除错误代码。
请与您当地的Schneider Electric 代表联系。
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[程序运行错误] PGrF
检查能否清除错误代码。
请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[输入缺相] PHF
• 变频器电源不正确或熔断器熔断。
• 电源中的一相不可用。
• 在三相变频器上使用单相电源。
• 负载不平衡。
• 检查电源连接和保险丝。
• 使用三相电源。
• 如果使用单相电源或直流母线电源,则将 [输入缺相] IPL 设置为 [否]
nO,即可禁止检测到的错误。
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[泵低流量错误] PLFF
泵低流量监控功能检测到了一个错误。
• 检查排放时阀是否关闭。
• 排放时损坏管道。
• 查找系统出口处出现低流量的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[安全功能故障] SAFF
• 超出去抖时间。
• 内部硬件错误。
• STOA 和STOB 具有不同状态(高/低)且持续超过 1 秒。
• 检查数字输入STOA 和 STOB 的接线.
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[电机短路] SCF1
变频器输出端短路或接地。
• 检查变频器与电机之间的电缆以及电机的绝缘情况。
• 调整开关频率。
• 在变频器与电机之间加装电抗器。
This detected error can be cleared manually with the [扩展故障复位] HRFC
parameter after the cause has been removed.
[接地短路] SCF3
如果并行连接多个电机,变频器输出端会有大量电流泄漏到地面。
• 检查变频器与电机之间的电缆以及电机的绝缘情况。
• 调整开关频率。
• 在变频器与电机之间加装电抗器。
• 如果使用长电缆,则检查 [接地故障激活] GrFL 的设置。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[IGBT 短路] SCF4
功率组件检测错误。
产品上电时,对IGBT 进行了测试,查看有无短路。 由此在至少一个 IGBT 上检测到错误(短路或开路)。 检查每个晶体管的时间介于 1 至 10 μs 之间。
检查 [输出短路测试] Strt 参数的设置。请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[电机短路] SCF5
变频器输出短路。
• 检查将变频器连接到电机的电缆以及电机绝缘情况。
• 请与您当地的Schneider Electric 代表联系。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AFE 短路故障] SCF
AFE 整流器IGBT 短路。
由于电网中的功率因数补偿系统而导致AFE 过电流。 电容器的每次开关都会在电源中产生过电压,从而导致 AFE 中出现过电流。
• 在安装有功率因数补偿系统且在电容投切时,检查电源电压。 仅安装带有集成电抗器的功率因数补偿系统。
• 检查将AFE 模块连接到电源的电缆。
• 请与您当地的Schneider Electric 代表联系。
This detected error requires a power reset.
[Modbus 通讯中断] SLF1
Modbus 端口通信中断。
• 检查通信总线。
• 检查超时。
• 参考Modbus 用户手册。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[PC 通讯中断] SLF2
与调试软件的通信中断。
• 检查调试软件的连接电缆。
• 检查超时。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[HMI 通信中断] SLF3
与图形显示终端的通信中断。
当使用图形显示终端提供命令或参考值,且通信中断超过 2 秒时,将触发此错误。
• 检查图形显示终端的连接。
• 检查超时。.
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[电机过速] SOF
• 不稳定或驱动负载过大。
• 如果使用下游接触器,则可能在应用运行命令前没有关闭电机与变频器之间的触点。
• 已达到过速阈值(对应于 [最大输出频率] TFR 的 110 %)。
• 检查电机参数设置。
• 检查电机/变频器/负载的大小。
• 在应用运行命令前,请检查并关闭电机与变频器之间的触点。
• 检查 [最大输出频率] TFR 与 [高速频率] HSP 之间的一致性。建议 [最大输出频率] TFR 至少大于等于 110% * [高速频率] HSP。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
[安全文件损坏] SPFC
安全文件损坏或缺失。
关闭产品电源。下次打开电源时,将再次创建安全文件,与网络安全相关的信息
(比如通道政策和密码)将被复位为默认值。
This detected error requires a power reset.
SHAPE \* MERGEFORMAT
[电机失速错误] StF
堵转监控功能检测到了一个错误。
以下条件下,将触发 [电机失速错误] STF:
• 输出频率小于 [堵转频率] STP3
• 输出电流大于 [堵转电流] STP2
• 持续时间超过 [堵转最大时间] STP1。
• 查找电机是否机械卡死。
• 查找电机出现过载的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI2 热传感器故障] t2CF
热传感器监控功能检测到了模拟输入 AI2 出现热传感器错误:
• 开路,或
• 短路。
• 检查传感器及其接线。
• 更换传感器。
• 检查 [AI2 类型] AI2T 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI3 热传感器错误] t3CF
热监控功能检测到连接到模拟输入 AI3 的热传感器出错:
• 开路,或
• 短路
• 检查传感器及其接线。
• 更换传感器。
• 检查 [AI3 类型] AI3T 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI4 热传感器错误] t4CF
热监控功能检测到连接到模拟输入 AI4 的热传感器出错:
• 开路,或
• 短路
• 检查传感器及其接线。
• 更换传感器。
• 检查 [AI4 类型] AI4T 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI5 热传感器错误] t5CF
热监控功能检测到连接到模拟输入 AI5 的热传感器出错:
• 开路,或
• 短路
• 检查传感器及其接线。
• 更换传感器。
• 检查 [AI5 类型] AI5T 参数的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [电机绕组A 分配] tFAA 的数字输入的有效时间超过 [电机绕组A 延时]
tFdA。
• 检查连接的设备(电机轴承热开关)及其接线。
• 验证电机负载情况和环境温度。 等待电机冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [电机绕组B 分配] tFAB 的数字输入的有效时间超过 [电机绕组B 延时]
tFdB。
• 检查连接的设备(电机轴承热开关)及其接线。
• 验证电机负载情况和环境温度。等待电机冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [电机轴承A 分配] tFAC 的数字输入的有效时间超过 [电机轴承A 延时]
tFdC。
• 检查连接的设备(电机轴承热开关)及其接线。
• 验证电机负载情况和环境温度。等待电机冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
分配至 [电机轴承B 分配] tFAD 的数字输入的有效时间超过 [电机轴承B 延时]
tFdD。
• 检查连接的设备(电机轴承热开关)及其接线。
• 验证电机负载情况和环境温度。等待电机冷却后再重新起动。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[AI2 热水平错误] tH2F
热传感器监控功能检测到了模拟输入 AI2 出现高温错误。
• 查找出现过热的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI3 热水平错误] tH3F
热传感器监控功能检测到模拟输入 AI3 上的温度过高。
• 查找出现过热的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[AI4 热水平错误] tH4F
热传感器监控功能检测到模拟输入 AI4 上的温度过高。
• 查找出现过热的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[AI5 热水平错误] tH5F
热传感器监控功能检测到模拟输入 AI5 上的温度过高。
• 查找出现过热的可能原因。
• 检查监控功能的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[IGBT 过热] tJF
变频器功率级过热。
• 根据环境条件,检查负载/电机/变频器的大小。
• 减小开关频率。
• 延长加减速时间。
• 降低电流限值。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
整流器IGBT 功率级过热。
• 根据环境条件,检查负载/电机/变频器的大小。
• 如果需要,检查并清洁冷却通道。
• 清洁或更换 IP54 产品上的滤垫。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
[自整定错误] tnF
• 特殊电机或功率与变频器不相符的电机。
• 电机未连接到变频器。
• 电机未停止。
• 检查电机/变频器是否匹配。
• 确保在自整定期间电机连接到变频器。
• 如果必须使用输出接触器,请在自整定期间将其闭合。
• 确保在自整定期间电机已连接且已停止。
• 对于磁阻电机,应降低 [PSI 最大电流比例] MCr。
This detected error can be cleared manually with the [故障复位分配] RSF
parameter after its cause has been removed.
SHAPE \* MERGEFORMAT
[过程欠载] ULF
过程欠载。
• 检查并清除欠载原因。
• 检查 [过程欠载] Uld- 功能的参数
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
• 电源欠压使直流总线电压过低。
• AFE 过载。
• 检查电源电压。
• 根据环境条件,检查负载/电机/变频器的大小。
This detected error is cleared as soon as its cause has been removed.
SHAPE \* MERGEFORMAT
[主电源欠压] USF
• 电源电压太低。
• 瞬变电压突降。
检查 [欠压处理] USb 的电压和参数。
This detected error is cleared as soon as its cause has been removed.
错误延迟 [错误延迟] VCFD 后仍存在无效功率给定值曲线或警告。
• 检查在预设模式 [预设曲线模式] PST下设置的功率与速度对比给定值曲线的参数是否有效。
• 检查 [学习速度过低] VCSJ 和 [学习速度过高]VCS 的设置。
This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.
用于异步和同步电机的变频器
如果显示屏未亮,请检查变频器的电源。
如果没有对相应数字输入通电,则快速停车或自由停车功能分配将会阻止变频器启动。然后,变频器将在自由停车时显示 [自由停车] nSt,而在快速停车时显示
[快速停车] FSt。这是正常行为,因为这些功能在零值时是激活的,以便变频器能在控制线路断开时停止。
确认按照选定的控制模式激活运行命令输入([2/3 线控制] tCC 和 [2 线类型]
tCt 参数)。
如果将给定通道或命令通道分配给现场总线,则在上电时,变频器将显示出 [自由停车] nSt。在现场总线发出命令之前,变频器将处于停止模式。
如果在以下操作过程中仍有诸如正向运行、反向运行、直流注入等运行命令在运行,则变频器将被锁定在阻断状态下并显示出 [自由停车] nSt:
• 产品重置为出厂设置;
• 使用 [故障复位分配] RsF 实现手动故障复位;
• 再次使用产品开关实现手动故障复位;
• 由通道发出的停止命令而非激活的通道命令(例如使用 2/3 线控制时的显示终端停止键);
必须在给出新的运行命令之前取消所有的活动运行命令。
当一个选件模块被拆卸或被另一模块替换时,变频器在通电时将锁定为 [不正确的配置] CFF 错误模式。如果有意更换或拆卸了选件模块,则检测到的错误可通过按两次 OK 键加以清除,这将导致受此选件模块影响的参数组被恢复为出厂设置。
如果用配有不同额定值的控制块更换现有控制块,则变频器在通电时将锁定为 [不正确的配置] CFF 错误模式。如果有意更换了控制块,则可按 OK 键两次来清除检测到的错误,此操作将导致恢复所有出厂设置。