施耐德变频器故障代码


[内部错误 23] InFN .......................................................................................................... 621

[内部错误 25] InFP .......................................................................................................... 622

[内部错误 27] InFr .......................................................................................................... 622

[内部错误 28] InFS .......................................................................................................... 623

[内部错误 29] InFt .......................................................................................................... 623

[内部错误 30] InFU .......................................................................................................... 624

[内部错误 31] InFV .......................................................................................................... 624

[入口压力错误] iPPF ........................................................................................................ 625






概述

清除检测到的错误


[自整定错误] tnF ................................................................................................................. 658

[过程欠载] ULF...................................................................................................................... 659

[AFE 主电源欠压] UrF ...................................................................................................... 659

[主电源欠压] USF................................................................................................................. 660

[VxCtrl 错误] vcf............................................................................................................. 660






如需对变频系统进行检修,请遵循下表指示的步骤:



步骤

操作

1

断开所有电源包括可能会带电的外部控制电源。

2

将所有电源隔离开关锁定在断电位置。

3

等待 15 分钟让直流母线电容充分放电变频器的LED 并不是有无直流母线电压的指示灯

4

测量PA/+ PC/- 端子之间的直流母线电压确保该电压低于 42 Vdc

5

如果直流母线电容未完全放电请与当地的施耐德电气办事处联系。不要对变频器进行修理或运行。

6

查找并纠正检测到的错误的原因。

7

恢复对变频器供电以确认已纠正检测到的错误。


故障原因消除后, 可以通过以下操作任一清除错误警告:

•       关闭变频器。

•       使用 [产品重启] RP 参数。

•       使用分配给 [产品重启分配] RPA 的数字输入或控制位。

•       使用 [故障自动复位] ATR- 功能。

•       数字输入或控制位设置为 [故障复位] RST- 功能。

◦       对于 [故障复位分配] RSF 和 [扩展故障复位] HRFC,请参阅 [故障复位]

RST- 菜单。

•       按图形显示终端上的停止/复位键,具体取决于 [停止键启用] PST 的设置。


如何清除错误代码?

下表总结了在消除原因后清除检测到的错误的可能性:


如何在消除原因后清除错误代码

已清除错误的列表

        关闭变频器。

        使用 [产品重启] RP 参数。

        使用分配给 [产品重启分配] RPA 的数字输入或控制位。

检测到的所有错误。

        消除原因后即清除。

CFF, CFI, CFI2, CFI3, CSF, FWER, HCF, PGLF, PHF, URF, USF

        使用分配给以下对象的数字输入或控制位

[故障复位分配] RSF.

        HMI 面板上的复位按钮。

ACF1, ACF2, ACF3, ASF, MFF, SOF, TNF



如何在消除原因后清除错误代码

已清除错误的列表

        使用分配给以下对象的数字输入或控制位

[故障复位分配] RSF.

        HMI 面板上的复位按钮。

        使用 [故障自动复位] ATR- 功能。

CFA, CFB, CFC, CHF, CNF, COF, COPF, DRYF, EPF1, EPF2, ETHF, FCF2, FDR1, FDR2, FFDF, HFPF, IDLF, IFA, IFB, IFC, IFD, IHF, INF9, INFB, INFV, IPPF, JAMF, LCF, LCHF, LCLF, LFF1, LFF2, LFF3, LFF4, LFF5, LKON, MDLF, MOF, MPDF, MPLF, OBF, OBF2, OHF, OLC, OLF, OPF1, OPF2, OPHF, OPLF, OSF, P24C, PCPF, PFMF, PLFF, SCF4, SCF5, SLF1, SLF2, SLF3, STF, T2CF, T3CF, T4CF, T5CF, TFA, TFB, TFC, TFD, TH2F, TH3F, TH4F, TH5F, TJF, TJF2, ULF

如果 [扩展故障复位] HRFC 设置为 YES

        使用分配给 [故障复位分配] RSF 的数字输入或控制位

        按图形显示终端上的停止/复位具体取决于 [停止键启用] PST 的设置。

CRF1, INFD, SCF1



SHAPE \* MERGEFORMAT


[AFE 直流电容器故障] ACF1



可能原因


AFE 直流电容器故障: 直流电容器过电流。

•       电源电压过低的持续时间过长。

•       电源电压达到下限,AFE 的调制率提高,有助于保护直流链路电容器,防止触发 [AFE 直流电容器故障]  ACF1。





补救措施


•       检查电源电压。

•       检查电源电压的参数设置。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



[AFE 电流控制故障] ACF2


可能原因


电源电压中断。





补救措施


•       检查电源电压。

•       降低电压下降次数。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AFE 线路滤波器故障] ACF3



可能原因


发电机运行期间出现电源电压下降。





补救措施


检查电源电压。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



[高级功能锁] AFLF



可能原因


[液位控制策略] LCst 设置为 [能效优化] ADV 并给出运行命令。





补救措施


请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[角度错误] ASF



可能原因


在相位移夹角测量过程中,如果电机相断开或电机电感太高,则会触发此错误。





解决措施


•       检查电机连接是否缺相,以及变频器允许的最大电流。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



[断路器故障] CbF


可能原因


在配置的 [电源电压超时] LCt过后,与断路器逻辑控制(启动或停止脉冲)相比,直流总线电压水平不正确。





补救措施


•       检查断路器逻辑控制(启动和停止的脉冲时间)。

•       检查断路器的机械状态。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[柜机电路 A 故障] CFA



可能原因


监控功能检测到了一个错误。 当检测到的故障的持续时间超过 [机柜电路A 延迟]

CFAA 时,分配至 [机柜电路 A 分配] FdA 的数字输入将被激活。





补救措施


•       确定检测的原因。

•       检查连接的设备(门开关、热开关等)及其接线。

•       检查 [机柜电路 A 分配] CFAA 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[机柜回路 B 故障] CFB


可能原因


监控功能检测到了一个错误。当检测到的故障的持续时间超过 [机柜电路B 延迟]

FdB 时,分配至 [机柜电路 B 分配] CFAB 的数字输入将被激活。





解决措施


•       确定检测的原因。

•       检查连接的设备(门开关、热开关等)及其接线。

•       检查 [机柜电路 B 分配] CFAB 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[柜机电路 C 故障] CFC



可能原因


监控功能检测到了一个错误。 当检测到的故障的持续时间超过 [机柜电路C 延迟]

CFAC 时,分配至 [机柜电路 C 分配] FdC 的数字输入将被激活。





补救措施


•       确定检测的原因。

•       检查连接的设备(门开关、热开关等)及其接线。

•       检查 [机柜电路 C 分配] CFAC 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[配置不正确] CFF


可能原因


•       选件模块已更换或拆除.

•       使用变频器上配置的具有不同额定值的控制卡替换现有控制卡。

•       当前配置不一致。





补救措施


•       检查选件模块上未出现检测出错误。

•       如果专门更换了控制块,请参阅以下注释。

•       如果允许,返回到出厂设置或恢复备份配置。




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[无效配置] CFI



可能原因


无效配置。

通过调试工具或现场总线加载至变频器的配置与变频器软硬件不一致。





解决措施


•       检查已加载的配置。

•       加载有效配置。




清除错误代码

This detected error is cleared as soon as its cause has been removed.


[配置传输错误] CFI2


可能原因


•       将配置传输到变频器的操作失败或中断。

•       加载的配置与该变频器不兼容。





补救措施


•       检查以前加载的配置。

•       载入兼容配置。

•       使用PC 软件调试工具传输兼容的配置

•       执行出厂设置




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[预设置传输故障] CFI3



可能原因


将配置传输到变频器的操作失败或中断。





解决措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error is cleared as soon as its cause has been removed.


[机柜过热故障] CHF


可能原因


机柜热开关处于激活状态,机柜风扇已开启,但无风扇反馈。

配有机柜 IO 的变频器的数字输入 DI50 和 DI51 配置为用于监测机柜温度。在温度过高的情况下,如果机箱温度开关打开,将触发 [机柜过热故障] CHF。

此错误只能在运行状态下触发。在其他状态下,将激活 [机柜过热警告CHA。





解决措施


•       检查机柜风扇及其接线。

•       检查机箱中的温度是否太高。

•       检查热开关的设置(必须为 60°C (140°F))





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[现场总线通信中断] CnF


可能原因


现场总线模块的通信中断。

当现场总线模块与主站(PLC) 之间的通信中断时,将触发此错误。





补救措施


•       检查环境(电磁兼容性)。

•       检查接线情况。

•       检查超时。

•       更换选件模块。

•       请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[CANopen 通讯中断] COF



可能原因


CANopen® 现场总线上的通信中断。





补救措施


•       检查通信总线。

•       检查超时。

•       请参考CANopen® 手册 (EAV64333), 15 页。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[冷却泵故障] COPF



可能原因


冷却泵未在工作。





补救措施


请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[预充电电容器] CrF1


可能原因


•       充电电路控制检测到了错误或充电电阻器损坏。

•       电源电压太低。





补救措施


•       对变频器断电再通电。

•       检查内部连接。

•       检查 [欠压处理] usb 的电压和参数。

•       请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared manually with the [扩展故障复位] HRFC

parameter after the cause has been removed.



SHAPE \* MERGEFORMAT


[AFE 接触器反馈错误] CrF3



可能原因


此错误在不同情况下发生(启动/停止/操作过程中)。

在每个AFE 功能块内部相互独立地分析此错误。 如果 AFE 电源接触器反馈信号与内部AFE 电源接触器命令不匹配,将会触发 [AFE 接触器反馈错误] CrF3。

执行运行命令时:

•       AFE 模块内部控制发送“主接触器开启命令”后,必须在 400 毫秒内收到“主接触器开启反馈”。

执行停止命令时:

•       在 AFE 模块内部控制已发送“主接触器关闭命令”后,必须在 500 毫秒内收到

主接触器关闭反馈





补救措施


•       检查与以下各项相关的环境(电磁兼容性):

◦       电缆敷设(控制单元和功率单元未混合)。

◦       接地线缆。

◦       接地屏蔽层。

•       检查将变频器连接到电机的电缆。

•       确定哪个 AFE 模块检测到 [AFE 接触器反馈错误] CrF3 错误,方法是将图形显示终端连接到 AFE 模块 HMI 端口并检查故障历史记录。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[通道切换错误] CSF



可能原因


切换到无效通道。





解决措施


检查功能参数。




清除错误代码

This detected error is cleared as soon as its cause has been removed.


[直流母线纹波错误] DCRE


可能原因


在直流母线或直流母线电容器损坏时观测到持续的纹波。





补救措施


•       对变频器断电再通电。

•       检查输入滤波器的行为是否正确。

•       检查电源接线。

•       检查内部连接。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[干泵运行错误] drYF



可能原因


干泵运行监控功能检测到了一个错误。

: 触发错误后,即使已清除检测到的错误,在 [干泵运行重启延时] dryr

结束前,也无法重启泵。





解决措施


•       检查泵已充分泡水。

•       检查入水管道有无漏气。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[EEPROM 控制] EEF1



可能原因


检测到了控制块的内存错误。





补救措施


•       检查环境(电磁兼容性)。

•       关闭产品电源。

•       还原出厂设置。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[EEPROM 功率] EEF2



可能原因


检测到了电源板的内存错误。





解决措施


•       检查环境(电磁兼容性)。

•       关闭产品电源。

•       还原出厂设置。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[外部错误] EPF1


可能原因


•       由外部设备触发的事件,由应用引起。

•       由嵌入式以太网触发的外部错误。

•       该错误由外部电路导致。

•       以太网配置文件损坏。





补救措施


•       消除外部错误的原因。

•       执行以太网配置的出厂设置或修改 IP 模式





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[现场总线错误] EPF2


可能原因


由外部设备触发的事件,由应用引起。





解决措施


消除外部错误的原因。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[嵌入式以太网通信中断] EtHF



可能原因


ModbusTCP 总线出现通信中断。





补救措施


•       检查通信总线。

•    请参阅以太网手册 (嵌入式(EAV64327), 15 页;选件(EAV64328), 15 页)。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[输出接触器闭合故障FCF1



可能原因


虽然符合打开条件,但输出接触器仍闭合。





补救措施


•       检查输出接触器及其接线。

•       检查接触器反馈接线。




清除错误代码

This detected error requires a power reset.


[输出接触器打开错误FCF2


可能原因


虽然符合闭合条件,但输出接触器仍打开。





补救措施


•       检查输出接触器及其接线。

•       检查接触器反馈接线。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[FDR 1 错误] FDR1



可能原因


•       嵌入式以太网FDR 错误

•       变频器和 PLC 之间的通信中断

•       配置文件不兼容、为空或无效

•       变频器额定值与配置文件不一致





解决措施


•       检查变频器和PLC 连接

•       检查通信工作负载

•       重新启动将配置文件从变频器到PLC 的传输





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[FDR 2 错误] FDR2



可能原因


•       以太网现场总线模块 FDR 故障

•       变频器和 PLC 之间的通信中断

•       配置文件不兼容、为空或损坏

•       变频器额定值与配置文件不一致





解决措施


•       检查变频器和PLC 连接

•       检查通信工作负载

•       重新启动将配置文件从变频器到PLC 的传输





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[风扇反馈错误] FFDF



可能原因


风机速度过低。

[风扇反馈警告] FFDA 已激活 10 分钟以上。





补救措施


更换风机。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[固件更新错误] FWEr


可能原因


固件更新功能检测到错误。





补救措施


•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[板兼容性] HCF


可能原因


硬件配置错误。

[配对密码] PPI 参数已启用,且选件模块被更换。





解决措施


•       重新安装原始选件模块。

•       如果已慎重更换该模块,则可通过输入 [配对密码] PPI 确认配置。




清除错误代码

This detected error is cleared as soon as its cause has been removed.


[高流量错误] HFPF



可能原因


流量高监控功能检测到了错误。





补救措施


•       检查系统是否在其流量范围内运行。

•       检查系统出口处的管道有无爆裂。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[节能退出错误] IDLF



可能原因


变频器未打开,即使 [节能超时] IDLT 已过。





补救措施


•       检查电源/接触器/变频器接线情况。

•       检查超时。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[监视回路 A 故障] IFA



可能原因


分配至 [监视回路A 分配] IFAA 的数字输入的有效时间超过 [监视回路A 延时]

IFdA。





解决措施


•       检查连接的设备及其接线。

•       检查 [监视回路 A 分配] IFAA 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[监视回路 B 故障] IFB



可能原因


分配至 [监视回路B 分配] IFAb 的数字输入的有效时间超过 [监视回路B 延时]

IFdB。





解决措施


•       检查连接的设备及其接线。

•       检查 [监视回路 B 分配] IFAB 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[监视回路 C 故障] IFC



可能原因


分配至 [监视回路C 分配] IFAC 的数字输入的有效时间超过 [监视回路C 延时]

IFdC。





解决措施


•       检查连接的设备及其接线。

•       检查 [监视回路 C 分配] IFAC 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[监视回路 D 故障] IFd



可能原因


分配至 [监视回路D 分配] IFAD 的数字输入的有效时间超过 [监视回路D 延时]

IFdD。





解决措施


•       检查连接的设备及其接线。

•       检查 [监视回路 D 分配] IFAD 参数的分配。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[输入过热] iHF



可能原因


AFE 功率模块温度过高。





补救措施


检查变频器通风情况和环境温度。 等待变频器冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[内部连接错误] ILF



可能原因


选件模块和变频器之间的通信中断。





解决措施


•       检查环境(电磁兼容性)。

•       检查连接状况。

•       更换选件模块。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 0] InF0



可能原因


•       控制板的微处理器之间的通信中断。

•       电源板额定功率无效。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 1] InF1



可能原因


电源板额定功率无效。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 2] InF2


可能原因


电源板与控制板软件不兼容。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.




可能原因


检测出内部通信错误。





补救措施


•       检查变频器控制端子(模拟输入的内部 10V 电源已超载)的接线。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 4] InF4



可能原因


内部数据不一致。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 6] InF



可能原因


•       安装在变频器中的选件无法识别。

•       不存在或无法识别可插拔的控制端子模块(如果有)。

•       无法识别嵌入式以太网适配器。





补救措施


•       与变频的固件版本的兼容性。

•       关闭变频器后,插入可插拔控制端子板。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 7] InF7


可能原因


与控制板的 CPLD 组件的通信中断。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 8] InF8



可能原因


内部开关电源工作不正常。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 9] InF9


可能原因


检测到了电流测量电路出错。





补救措施


请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[内部错误 10] InFA



可能原因


电源整流部分未正常工作。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 11] InFb


可能原因


变频器内部的热传感器无法正常工作。




补救措施

Contact your local Schneider Electric representative.



清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[内部错误 12] InFC



可能原因


内部供电错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 13] InFD



可能原因


差分电流偏差。





补救措施


检查DigiLink 电缆 (GG45) 的连接。

请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared manually with the [扩展故障复位] HRFC

parameter after the cause has been removed.



SHAPE \* MERGEFORMAT


[内部错误 14] InFE



可能原因


检测到内部微处理器出错。





补救措施


•       检查能否清除错误代码。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 15] InFF


可能原因


串行存储器闪存格式错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 16] InFG



可能原因


输出继电器选件模块的通信中断或内部出错。





补救措施


•       检查选件模块是否正确连接到插槽

•       更换选件模块。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 17] InFH


可能原因


与数字与模拟I/O 扩展模块通信中断或数字与模拟I/O 扩展模块出现内部错误。





补救措施


•       检查选件模块是否正确连接到插槽

•       更换选件模块。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 20] InF



可能原因


选件模块接口板错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误21] InFl



可能原因


内部实时时钟错误。这可能是面板与变频器之间出现通信错误或时钟振荡器启动出错。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 22] InF



可能原因


检测到了嵌入式以太网适配器错误。





补救措施


检查与以太网端口的连接。

请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 23] InFN


可能原因


检测到控制块和AFE BU 模块之间的通讯中断。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 25] InFP



可能原因


控制板硬件版本与固件版本之间不兼容。





补救措施


•       更新固件包。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 27] InFr



可能原因


CPLD 中的诊断功能已检测到错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 28] InFS



可能原因


检测到AFE 模块上出现错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[内部错误 29] InFt



可能原因


检测到功率模块/ 逆变器模块上出现错误。





补救措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[内部错误 30] InFU



可能原因


检测到整流器模块上出现错误,或在为直流总线充电时触发了  [输入缺相] PHF





补救措施


对变频器断电再通电。

如果 [输入缺相] PHF 错误代码替换了 [内部错误 30] inFu,请参阅 [输入缺相] PHF 错误的说明,其他情况下,请联系您当地的 Schneider Electric 代表。




清除错误代码

This detected error requires a power reset.


[内部错误 31] InFV


可能原因


检测到程序块架构出错(程序块丢失)。





补救措施


与当地的 Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[入口压力错误] iPPF



可能原因


入口压力监控功能检测到了错误。





补救措施


•       查找系统入口出现低压的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[防堵塞错误] JA   F



可能原因


防堵塞监控功能超出了时间窗口所规定的最大正反转动作时序数。





补救措施


•       查找叶轮的堵塞物质。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[输入接触器] LCF



可能原因


尽管 [输入电压超时监测] LCt 已过,变频器仍未启动。





补救措施


•       检查输入接触器及其接线。

•       检查 [输入电压超时] LCt。

•       检查电源/接触器/变频器接线。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[高电平错误] LCHF



可能原因


注水过程中已激活最高液位开关。





补救措施


•       检查参数 [最高液位切换分配] LCWH。

•       检查相应变频器输入及其接线的状态。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[低液位错误] LCLF



可能原因


排空过程中已激活最低液位开关。





补救措施


•       检查参数 [最低液位切换分配] LCWL。

•       检查相应变频器输入及其接线的状态。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AI1 4-20mA 丢失] LFF1



可能原因


模拟输入 AI1 丢失 4-20 mA 信号。

当测得的电流小于 2 mA 时,将触发此错误。





解决措施


•       检查模拟输入的连接。

•       检查 [AI1 4-20mA 丢失] LFL1 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI2 4-20mA 丢失] LFF2


可能原因


模拟输入 AI2 损失 4-20 mA

当测得的电流小于 2 mA 时,将触发此错误。





补救措施


•       检查模拟输入的连接。

•       检查 [AI2 4-20mA 丢失] LFL2 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AI3 4-20mA 丢失] LFF3



可能原因


模拟输入 AI3 上损失 4-20 mA

当测得的电流小于 2 mA 时,将触发此错误。





解决措施


•       检查模拟输入的连接。

•       检查 [AI3 4-20mA 丢失] LFL3 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI4 4-20mA 丢失] LFF4


可能原因


模拟输入 AI4 丢失 4-20 mA 信号。

当测得的电流小于 2mA 时,将触发此错误。





解决措施


•       检查模拟输入的连接。

•       检查 [AI4 4-20mA 丢失] LFL4 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AI5 4-20mA 丢失] LFF5



可能原因


模拟输入 AI5 丢失 4-20 mA 信号。

当测得的电流小于 2 mA 时,将触发此错误。





解决措施


•       检查模拟输入的连接。

•       检查 [AI5 4-20mA 丢失] LFL5 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[上电锁定错误] L  ON



可能原因


外部设备未就绪。





补救措施


检查外部设备是否分配至上电锁定输入。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[MDL 故障dLF


可能原因


•       运行时通信中断。

•       此功能检测到系统配置的不一致性。





解决措施


•       检查通信网络。

•       检查多变频器链路功能的配置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[电源频率超出范围]   FF



可能原因


AFE 模块上的[电源频率] FAC 超出范围。





补救措施


检查电源频率。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



[模块过热]   OF


可能原因


机柜温度过高。

[模块过热]     OA 警告已激活 10 分钟以上。





补救措施


检查机柜的冷却情况。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[多泵设备故障]    PDF



可能原因


多变频器链接架构上的一个设备缺失。





补救措施


检查通信网络。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[主泵故障]   pLF



可能原因


选定主泵在运行中不可用。





补救措施


检查对应的变频器数字输入的状态,了解泵可用性信息(例如,对于泵 1,查看

[ 1 就绪分配]    PI1)。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[直流总线过压] ObF


可能原因


•       减速时间太短或驱动性负载太高。

•       供电电源电压过高。





补救措施


•       延长减速时间。

•       在与该应用兼容的前提下配置 [减速斜坡自适应]brA 功能。

•       检查电源电压。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AFE 母线不平衡] ObF2


可能原因


•       AFE 直流母线不平衡。

•       供电电源电压过高。

•       总发电量太高





补救措施


•       检查电源电压。

•       请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[过流] OCF


可能原因


•      [电机数据]      OA- 菜单中的中的参数不正确。

•       惯量或负载过高。

•       机械堵塞。





补救措施


•       检查电机参数。

•       检查电机/变频器/负载的大小。

•       检查机械装置的状态。

•       减小 [电流限制] CLI。

•       增加开关频率。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[变频器过热] OHF



可能原因


变频器温度过高。





解决措施


检查电机负载、变频器通风情况和环境温度。等待变频器冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[过程过载] OLC


可能原因


过程过载。





解决措施


•       检查并消除引起过载的原因。

•       检查 [过程过载] OLd- 功能的参数。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[电机过载] OLF


可能原因


因电机电流持续过大而触发。





解决措施


•       检查电机热监控的设置

•       检查电机负载。等待电机冷却后再重新启动。

•       检查以下参数的设置:

◦       [电机热电流] ITH

◦       [电机热保护类型] THT

◦       [电机热阈值] TTD

◦       [电机过热响应] OLL




清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[一相输出丢失] OPF1


可能原因


变频器输出中缺少一相。





解决措施


检查变频器与电机的接线。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[输出缺相] OPF2



可能原因


•       电机未连接或电机功率太低。

•       输出接触器打开。

•       电机电流瞬间不稳定。





补救措施


•       检查变频器与电机的接线。

•       如果正在使用输出接触器,请将 [输出缺相分配] OPL 设置为 [未触发错误]

OAC

•       如果变频器已连接一个低功率电机或未连接电机: 在出厂设置模式中,激活电机缺相检测 [输出缺相] OPL = [触发输出缺相] YES。 禁用电机缺相检测

[输出缺相] OPL = [功能未激活] nO。

•       检查并优化下列参数: [IR 定子压降补偿] UFr、[电机额定电压] UnS 以及 [电机额定电流] nCr 并执行 [自整定] tUn。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[出口压力高] OPHF


可能原因


出口压力监控功能检测到了压力过高错误。





补救措施


•       查找系统出口出现高压的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[出口压力低] OPLF


可能原因


出口压力监控功能检测到了压力过低错误。





补救措施


•       检查系统出口处的管道有无损坏。

•       查找系统出口出现低压的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[供电电源过电压] OSF



可能原因


•       供电电源电压过高。

•       供电电源受到干扰。





解决措施


检查电源电压。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[机柜I/O 24V 错误] P24C



可能原因


输入DI58 用于监控输入端子上的 24V 电源。 如果出现故障,则抑制所有输入以避免意外错误消息(从软件版本V1.6V1.3 开始)。

•       DI58 机柜 I/O 输入未连接到内部端子X231。

•       DI58 由另一机柜 I/O 功能使用。





补救措施


•       确认端子 X231 是否已连接到机柜 I/O 输入 DI58。

•       如果DI58 由另一机柜功能使用,则需要将该功能更改为X220 端子上的另一可用机柜 I/O 输入。 此外,还需要调整新的所选输入的参数设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[泵循环启动错误PCPF



可能原因


泵循环监控功能超出了时间窗口所规定的最大启动序列数目。





解决措施


•       查找系统重复启动的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[PID 反馈错误] PF  F



可能原因


PID 反馈错误在时间窗口内超出了设定点周围的允许范围。





解决措施


•       检查管道是否有机械故障。

•       检查是否存在漏水现象。

•       检查是否打开了排放阀。

•       检查是否打开了消防栓。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[程序加载错误] PGLF


可能原因


检查能否清除错误代码。





解决措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[程序运行错误] PGrF



可能原因


检查能否清除错误代码。





解决措施


请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[输入缺相] PHF



可能原因


•       变频器电源不正确或熔断器熔断。

•       电源中的一相不可用。

•       在三相变频器上使用单相电源。

•       负载不平衡。





补救措施


•       检查电源连接和保险丝。

•       使用三相电源。

•       如果使用单相电源或直流母线电源,则将 [输入缺相] IPL 设置为 []

nO,即可禁止检测到的错误。




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[泵低流量错误] PLFF



可能原因


泵低流量监控功能检测到了一个错误。





补救措施


•       检查排放时阀是否关闭。

•       排放时损坏管道。

•       查找系统出口处出现低流量的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[安全功能故障] SAFF


可能原因


•       超出去抖时间。

•       内部硬件错误。

•       STOA 和STOB 具有不同状态(高/低)且持续超过 1 秒。





补救措施


•       检查数字输入STOA 和 STOB 的接线.

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[电机短路] SCF1



可能原因


变频器输出端短路或接地。





补救措施


•       检查变频器与电机之间的电缆以及电机的绝缘情况。

•       调整开关频率。

•       在变频器与电机之间加装电抗器。





清除错误代码


This detected error can be cleared manually with the [扩展故障复位] HRFC

parameter after the cause has been removed.



[接地短路] SCF3


可能原因


如果并行连接多个电机,变频器输出端会有大量电流泄漏到地面。





补救措施


•       检查变频器与电机之间的电缆以及电机的绝缘情况。

•       调整开关频率。

•       在变频器与电机之间加装电抗器。

•       如果使用长电缆,则检查 [接地故障激活] GrFL 的设置。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[IGBT 短路] SCF4



可能原因


功率组件检测错误。

产品上电时,对IGBT 进行了测试,查看有无短路。 由此在至少一个 IGBT 上检测到错误(短路或开路)。 检查每个晶体管的时间介于 1 10 μs 之间。





补救措施


检查 [输出短路测试] Strt 参数的设置。请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[电机短路] SCF5



可能原因


变频器输出短路。





补救措施


•       检查将变频器连接到电机的电缆以及电机绝缘情况。

•       请与您当地的Schneider Electric 代表联系。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AFE 短路故障] SCF



可能原因


AFE 整流器IGBT 短路。

由于电网中的功率因数补偿系统而导致AFE 过电流。 电容器的每次开关都会在电源中产生过电压,从而导致 AFE 中出现过电流。





补救措施


•       在安装有功率因数补偿系统且在电容投切时,检查电源电压。 仅安装带有集成电抗器的功率因数补偿系统。

•       检查将AFE 模块连接到电源的电缆。

•       请与您当地的Schneider Electric 代表联系。




清除错误代码

This detected error requires a power reset.


[Modbus 通讯中断] SLF1


可能原因


Modbus 端口通信中断。





解决措施


•       检查通信总线。

•       检查超时。

•       参考Modbus 用户手册。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[PC 通讯中断] SLF2



可能原因


与调试软件的通信中断。





解决措施


•       检查调试软件的连接电缆。

•       检查超时。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[HMI 通信中断] SLF3


可能原因


与图形显示终端的通信中断。

当使用图形显示终端提供命令或参考值,且通信中断超过 2 秒时,将触发此错误。





补救措施


•       检查图形显示终端的连接。

•       检查超时。.



清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[电机过速] SOF


可能原因


•       不稳定或驱动负载过大。

•       如果使用下游接触器,则可能在应用运行命令前没有关闭电机与变频器之间的触点。

•       已达到过速阈值(对应于 [最大输出频率] TFR 的 110 %)。





解决措施


•       检查电机参数设置。

•       检查电机/变频器/负载的大小。

•       在应用运行命令前,请检查并关闭电机与变频器之间的触点。

•       检查 [最大输出频率] TFR 与 [高速频率] HSP 之间的一致性。建议 [最大输出频率] TFR 至少大于等于 110% * [高速频率] HSP。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



[安全文件损坏] SPFC



可能原因


安全文件损坏或缺失。





解决措施


关闭产品电源。下次打开电源时,将再次创建安全文件,与网络安全相关的信息

(比如通道政策和密码)将被复位为默认值。




清除错误代码

This detected error requires a power reset.



SHAPE \* MERGEFORMAT


[电机失速错误] StF



可能原因


堵转监控功能检测到了一个错误。

以下条件下,将触发 [电机失速错误] STF:

•       输出频率小于 [堵转频率] STP3

•       输出电流大于 [堵转电流] STP2

•       持续时间超过 [堵转最大时间] STP1。





解决措施


•       查找电机是否机械卡死。

•       查找电机出现过载的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI2 热传感器故障] t2CF



可能原因


热传感器监控功能检测到了模拟输入 AI2 出现热传感器错误:

•       开路,或

•       短路。





补救措施


•       检查传感器及其接线。

•       更换传感器。

•       检查 [AI2 类型] AI2T 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI3 热传感器错误] t3CF



可能原因


热监控功能检测到连接到模拟输入 AI3 的热传感器出错:

•       开路,或

•       短路





解决措施


•       检查传感器及其接线。

•       更换传感器。

•       检查 [AI3 类型] AI3T 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI4 热传感器错误] t4CF



可能原因


热监控功能检测到连接到模拟输入 AI4 的热传感器出错:

•       开路,或

•       短路





解决措施


•       检查传感器及其接线。

•       更换传感器。

•       检查 [AI4 类型] AI4T 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI5 热传感器错误] t5CF



可能原因


热监控功能检测到连接到模拟输入 AI5 的热传感器出错:

•       开路,或

•       短路





解决措施


•       检查传感器及其接线。

•       更换传感器。

•       检查 [AI5 类型] AI5T 参数的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[电机绕组 A 故障] tFA



可能原因


分配至 [电机绕组A 分配] tFAA 的数字输入的有效时间超过 [电机绕组A 延时]

tFdA。





补救措施


•       检查连接的设备(电机轴承热开关)及其接线。

•       验证电机负载情况和环境温度。 等待电机冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[电机绕组 B 故障] tFB


可能原因


分配至 [电机绕组B 分配] tFAB 的数字输入的有效时间超过 [电机绕组B 延时]

tFdB。





解决措施


•       检查连接的设备(电机轴承热开关)及其接线。

•       验证电机负载情况和环境温度。等待电机冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[电机轴承 A 故障] tFC


可能原因


分配至 [电机轴承A 分配] tFAC 的数字输入的有效时间超过 [电机轴承A 延时]

tFdC。





解决措施


•       检查连接的设备(电机轴承热开关)及其接线。

•       验证电机负载情况和环境温度。等待电机冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[电机轴承 B 故障] tFD



可能原因


分配至 [电机轴承B 分配] tFAD 的数字输入的有效时间超过 [电机轴承B 延时]

tFdD。





解决措施


•       检查连接的设备(电机轴承热开关)及其接线。

•       验证电机负载情况和环境温度。等待电机冷却后再重新起动。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AI2 热水平错误] tH2F



可能原因


热传感器监控功能检测到了模拟输入 AI2 出现高温错误。





补救措施


•       查找出现过热的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI3 热水平错误] tH3F



可能原因


热传感器监控功能检测到模拟输入 AI3 上的温度过高。





解决措施


•       查找出现过热的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AI4 热水平错误] tH4F



可能原因


热传感器监控功能检测到模拟输入 AI4 上的温度过高。





解决措施


•       查找出现过热的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AI5 热水平错误] tH5F



可能原因


热传感器监控功能检测到模拟输入 AI5 上的温度过高。





解决措施


•       查找出现过热的可能原因。

•       检查监控功能的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[IGBT 过热] tJF



可能原因


变频器功率级过热。





补救措施


•       根据环境条件,检查负载/电机/变频器的大小。

•       减小开关频率。

•       延长加减速时间。

•       降低电流限值。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[AFE IGBT 过热故障] tJF2



可能原因


整流器IGBT 功率级过热。





补救措施


•       根据环境条件,检查负载/电机/变频器的大小。

•       如果需要,检查并清洁冷却通道。

•       清洁或更换 IP54 产品上的滤垫。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[自整定错误] tnF


可能原因


•       特殊电机或功率与变频器不相符的电机。

•       电机未连接到变频器。

•       电机未停止。





补救措施


•       检查电机/变频器是否匹配。

•       确保在自整定期间电机连接到变频器。

•       如果必须使用输出接触器,请在自整定期间将其闭合。

•       确保在自整定期间电机已连接且已停止。

•       对于磁阻电机,应降低 [PSI 最大电流比例] MCr。





清除错误代码


This detected error can be cleared manually with the [故障复位分配] RSF

parameter after its cause has been removed.



SHAPE \* MERGEFORMAT


[过程欠载] ULF


可能原因


过程欠载。





解决措施


•       检查并清除欠载原因。

•       检查 [过程欠载] Uld- 功能的参数





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.



[AFE 主电源欠压] UrF


可能原因


•       电源欠压使直流总线电压过低。

•       AFE 过载。





补救措施


•       检查电源电压。

•       根据环境条件,检查负载/电机/变频器的大小。




清除错误代码

This detected error is cleared as soon as its cause has been removed.



SHAPE \* MERGEFORMAT


[主电源欠压] USF



可能原因


•       电源电压太低。

•       瞬变电压突降。





解决措施


检查 [欠压处理] USb 的电压和参数。




清除错误代码

This detected error is cleared as soon as its cause has been removed.


[VxCtrl 错误] vcf



可能原因


错误延迟  [错误延迟VCFD 后仍存在无效功率给定值曲线或警告。





补救措施


•       检查在预设模式 [预设曲线模式] PST下设置的功率与速度对比给定值曲线的参数是否有效。

•      检查 [学习速度过低] VCSJ 和 [学习速度过高]VCS    的设置。





清除错误代码


This detected error can be cleared with the [故障自动复位] ATR or manually with the [故障复位分配] RSF parameter after its cause has been removed.


用于异步和同步电机的变频器

FAQ(常见问题解答)

简介

如果显示屏未亮,请检查变频器的电源。

如果没有对相应数字输入通电,则快速停车或自由停车功能分配将会阻止变频器启动。然后,变频器将在自由停车时显示 [自由停车] nSt,而在快速停车时显示

[快速停车] FSt。这是正常行为,因为这些功能在零值时是激活的,以便变频器能在控制线路断开时停止。

确认按照选定的控制模式激活运行命令输入([2/3 线控制] tCC 和 [2 线类型]

tCt 参数)。

如果将给定通道或命令通道分配给现场总线,则在上电时,变频器将显示出 [自由停车] nSt。在现场总线发出命令之前,变频器将处于停止模式。


变频器锁定在阻断状态下

如果在以下操作过程中仍有诸如正向运行、反向运行、直流注入等运行命令在运行,则变频器将被锁定在阻断状态下并显示出 [自由停车] nSt:

•       产品重置为出厂设置;

•       使用 [故障复位分配] RsF 实现手动故障复位;

•       再次使用产品开关实现手动故障复位;

•       由通道发出的停止命令而非激活的通道命令(例如使用 2/3 线控制时的显示终端停止键);

必须在给出新的运行命令之前取消所有的活动运行命令。


选件模块的更换或拆卸

当一个选件模块被拆卸或被另一模块替换时,变频器在通电时将锁定为 [不正确的配置] CFF 错误模式。如果有意更换或拆卸了选件模块,则检测到的错误可通过按两次 OK 键加以清除,这将导致受此选件模块影响的参数组被恢复为出厂设置。



更换控制块


如果用配有不同额定值的控制块更换现有控制块,则变频器在通电时将锁定为 [不正确的配置] CFF 错误模式。如果有意更换了控制块,则可按 OK 键两次来清除检测到的错误,此操作将导致恢复所有出厂设置。